125 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 50 m (164.0 ft).
Copper Cable (≤3% Drop)35 mm²Drop: 6.62V (1.65%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.46V (1.36%)
Voltage at Load393.4 VLine Loss: 1433.0 W
Max Power & Breaker86.6 kW125A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 154.44 V (38.61%) | 245.6 V | 254.76 V (63.69%) | 33437.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 20062.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 57.92 V (14.48%) | 342.1 V | 95.53 V (23.88%) | 12539.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 38.61 V (9.65%) | 361.4 V | 63.69 V (15.92%) | 8359.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.17 V (5.79%) | 376.8 V | 38.21 V (9.55%) | 5015.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.48 V (3.62%) | 385.5 V | 23.88 V (5.97%) | 3134.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 2006.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 6.62 V (1.65%) | 393.4 V | 10.92 V (2.73%) | 1433.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 4.63 V (1.16%) | 395.4 V | 7.64 V (1.91%) | 1003.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 3.31 V (0.83%) | 396.7 V | 5.46 V (1.36%) | 716.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.44 V (0.61%) | 397.6 V | 4.02 V (1.01%) | 528.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.93 V (0.48%) | 398.1 V | 3.18 V (0.8%) | 418.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.54 V (0.39%) | 398.5 V | 2.55 V (0.64%) | 334.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.25 V (0.31%) | 398.7 V | 2.07 V (0.52%) | 271.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.97 V (0.24%) | 399.0 V | 1.59 V (0.4%) | 209.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.77 V (0.19%) | 399.2 V | 1.27 V (0.32%) | 167.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.58 V (0.14%) | 399.4 V | 0.96 V (0.24%) | 125.4 W | ✓ OK (≤3%) |
FAQ — 125 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 125A at 50 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 50m at 400V (voltage drop: 6.62V or 1.65%).
What is the power capacity of 125A at 400V?
At unity power factor, 125A at 400V supports 86.6 kW with a standard 125A circuit breaker.
Related Lengths & Currents (400V)
125A · 5m (400V)125A · 10m (400V)125A · 15m (400V)125A · 20m (400V)125A · 25m (400V)125A · 30m (400V)125A · 35m (400V)125A · 40m (400V)125A · 45m (400V)125A · 60m (400V)125A · 70m (400V)10A · 50m (400V)16A · 50m (400V)20A · 50m (400V)25A · 50m (400V)32A · 50m (400V)40A · 50m (400V)50A · 50m (400V)63A · 50m (400V)80A · 50m (400V)100A · 50m (400V)160A · 50m (400V)200A · 50m (400V)