20 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 5.93V (1.48%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 6.11V (1.53%)
Voltage at Load394.1 VLine Loss: 205.4 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.88 V (2.47%)390.1 V16.3 V (4.08%)342.4 WDrop High
2.5 mm²24 A18 A5.93 V (1.48%)394.1 V9.78 V (2.45%)205.4 W✓ OK (≤3%)
4 mm²32 A25 A3.71 V (0.93%)396.3 V6.11 V (1.53%)128.4 W✓ OK (≤3%)
6 mm²41 A32 A2.47 V (0.62%)397.5 V4.08 V (1.02%)85.6 W✓ OK (≤3%)
10 mm²57 A44 A1.48 V (0.37%)398.5 V2.45 V (0.61%)51.4 W✓ OK (≤3%)
16 mm²76 A59 A0.93 V (0.23%)399.1 V1.53 V (0.38%)32.1 W✓ OK (≤3%)
25 mm²101 A78 A0.59 V (0.15%)399.4 V0.98 V (0.24%)20.5 W✓ OK (≤3%)
35 mm²125 A97 A0.42 V (0.11%)399.6 V0.7 V (0.17%)14.7 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.07%)399.7 V0.49 V (0.12%)10.3 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.05%)399.8 V0.35 V (0.09%)7.3 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.04%)399.8 V0.26 V (0.06%)5.4 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.03%)399.9 V0.2 V (0.05%)4.3 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.02%)399.9 V0.16 V (0.04%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.02%)399.9 V0.13 V (0.03%)2.8 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.02%)399.9 V0.1 V (0.03%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.3 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 20A at 20 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 20A over 20m at 400V (voltage drop: 5.93V or 1.48%).

What is the power capacity of 20A at 400V?

At unity power factor, 20A at 400V supports 13.86 kW with a standard 20A circuit breaker.