⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

40 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 1.24V (0.31%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.22V (0.31%)
Voltage at Load398.8 VLine Loss: 85.6 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.94 V (1.24%)395.1 V8.15 V (2.04%)342.4 WDrop High
2.5 mm²24 A18 A2.97 V (0.74%)397.0 V4.89 V (1.22%)205.4 WDrop High
4 mm²32 A25 A1.85 V (0.46%)398.1 V3.06 V (0.76%)128.4 WDrop High
6 mm²41 A32 A1.24 V (0.31%)398.8 V2.04 V (0.51%)85.6 W✓ OK (≤3%)
10 mm²57 A44 A0.74 V (0.19%)399.3 V1.22 V (0.31%)51.4 W✓ OK (≤3%)
16 mm²76 A59 A0.46 V (0.12%)399.5 V0.76 V (0.19%)32.1 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.07%)399.7 V0.49 V (0.12%)20.5 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.05%)399.8 V0.35 V (0.09%)14.7 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.04%)399.9 V0.24 V (0.06%)10.3 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.03%)399.9 V0.17 V (0.04%)7.3 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.02%)399.9 V0.13 V (0.03%)5.4 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.02%)399.9 V0.1 V (0.03%)4.3 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.01%)400.0 V0.08 V (0.02%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.01%)400.0 V0.07 V (0.02%)2.8 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)400.0 V0.05 V (0.01%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)400.0 V0.04 V (0.01%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)400.0 V0.03 V (0.01%)1.3 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 40A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 40A over 5m at 400V (voltage drop: 1.24V or 0.31%).

What is the power capacity of 40A at 400V?

At unity power factor, 40A at 400V supports 27.71 kW with a standard 40A circuit breaker.