50 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 5.56V (1.39%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.73V (1.43%)
Voltage at Load394.4 VLine Loss: 481.5 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)3210.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1926.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)1203.8 WDrop High
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)802.5 WDrop High
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)481.5 W✓ OK (≤3%)
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)300.9 W✓ OK (≤3%)
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)192.6 W✓ OK (≤3%)
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)137.6 W✓ OK (≤3%)
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)96.3 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)68.8 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)50.7 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)40.1 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)32.1 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)26.0 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)20.1 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)16.1 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)12.0 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 50A at 30 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 50A over 30m at 400V (voltage drop: 5.56V or 1.39%).

What is the power capacity of 50A at 400V?

At unity power factor, 50A at 400V supports 34.64 kW with a standard 50A circuit breaker.