80 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 4.74V (1.19%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.59V (1.4%)
Voltage at Load395.3 VLine Loss: 657.4 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.07 V (19.77%)320.9 V130.43 V (32.61%)10956.8 WDrop High
2.5 mm²24 A18 A47.44 V (11.86%)352.6 V78.26 V (19.57%)6574.1 WDrop High
4 mm²32 A25 A29.65 V (7.41%)370.3 V48.91 V (12.23%)4108.8 WDrop High
6 mm²41 A32 A19.77 V (4.94%)380.2 V32.61 V (8.15%)2739.2 WDrop High
10 mm²57 A44 A11.86 V (2.97%)388.1 V19.57 V (4.89%)1643.5 WDrop High
16 mm²76 A59 A7.41 V (1.85%)392.6 V12.23 V (3.06%)1027.2 WDrop High
25 mm²101 A78 A4.74 V (1.19%)395.3 V7.83 V (1.96%)657.4 W✓ OK (≤3%)
35 mm²125 A97 A3.39 V (0.85%)396.6 V5.59 V (1.4%)469.6 W✓ OK (≤3%)
50 mm²151 A118 A2.37 V (0.59%)397.6 V3.91 V (0.98%)328.7 W✓ OK (≤3%)
70 mm²192 A150 A1.69 V (0.42%)398.3 V2.8 V (0.7%)234.8 W✓ OK (≤3%)
95 mm²232 A181 A1.25 V (0.31%)398.8 V2.06 V (0.51%)173.0 W✓ OK (≤3%)
120 mm²269 A210 A0.99 V (0.25%)399.0 V1.63 V (0.41%)137.0 W✓ OK (≤3%)
150 mm²309 A241 A0.79 V (0.2%)399.2 V1.3 V (0.33%)109.6 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.16%)399.4 V1.06 V (0.26%)88.8 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)399.5 V0.82 V (0.2%)68.5 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.1%)399.6 V0.65 V (0.16%)54.8 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.07%)399.7 V0.49 V (0.12%)41.1 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 80A at 40 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 40m at 400V (voltage drop: 4.74V or 1.19%).

What is the power capacity of 80A at 400V?

At unity power factor, 80A at 400V supports 55.43 kW with a standard 80A circuit breaker.