Kabeltværsnit for 16 Ampere ved 45 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 45 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 10.67V (2.67%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 11.01V (2.75%)
Voltage at Load389.3 VLine Loss: 295.8 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.79 V (4.45%)382.2 V29.35 V (7.34%)493.1 W~ ≤5%
2.5 mm²24 A18 A10.67 V (2.67%)389.3 V17.61 V (4.4%)295.8 W✓ OK (≤3%)
4 mm²32 A25 A6.67 V (1.67%)393.3 V11.01 V (2.75%)184.9 W✓ OK (≤3%)
6 mm²41 A32 A4.45 V (1.11%)395.6 V7.34 V (1.83%)123.3 W✓ OK (≤3%)
10 mm²57 A44 A2.67 V (0.67%)397.3 V4.4 V (1.1%)74.0 W✓ OK (≤3%)
16 mm²76 A59 A1.67 V (0.42%)398.3 V2.75 V (0.69%)46.2 W✓ OK (≤3%)
25 mm²101 A78 A1.07 V (0.27%)398.9 V1.76 V (0.44%)29.6 W✓ OK (≤3%)
35 mm²125 A97 A0.76 V (0.19%)399.2 V1.26 V (0.31%)21.1 W✓ OK (≤3%)
50 mm²151 A118 A0.53 V (0.13%)399.5 V0.88 V (0.22%)14.8 W✓ OK (≤3%)
70 mm²192 A150 A0.38 V (0.1%)399.6 V0.63 V (0.16%)10.6 W✓ OK (≤3%)
95 mm²232 A181 A0.28 V (0.07%)399.7 V0.46 V (0.12%)7.8 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.06%)399.8 V0.37 V (0.09%)6.2 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.04%)399.8 V0.29 V (0.07%)4.9 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.04%)399.9 V0.24 V (0.06%)4.0 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.03%)399.9 V0.18 V (0.05%)3.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)399.9 V0.15 V (0.04%)2.5 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.11 V (0.03%)1.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 45 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 45 meter (400V)?

Til 16 Ampere over 45 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 10.67V / 2.67%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.