Kabeltværsnit for 16 Ampere ved 45 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 45 m ved 400V.
Copper Cable (≤3% Drop)2.5 mm²Drop: 10.67V (2.67%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 11.01V (2.75%)
Voltage at Load389.3 VLine Loss: 295.8 W
Max Power & Breaker11.09 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 17.79 V (4.45%) | 382.2 V | 29.35 V (7.34%) | 493.1 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 10.67 V (2.67%) | 389.3 V | 17.61 V (4.4%) | 295.8 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 6.67 V (1.67%) | 393.3 V | 11.01 V (2.75%) | 184.9 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 4.45 V (1.11%) | 395.6 V | 7.34 V (1.83%) | 123.3 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.67 V (0.67%) | 397.3 V | 4.4 V (1.1%) | 74.0 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 46.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.07 V (0.27%) | 398.9 V | 1.76 V (0.44%) | 29.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.76 V (0.19%) | 399.2 V | 1.26 V (0.31%) | 21.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.53 V (0.13%) | 399.5 V | 0.88 V (0.22%) | 14.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.38 V (0.1%) | 399.6 V | 0.63 V (0.16%) | 10.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.12%) | 7.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.22 V (0.06%) | 399.8 V | 0.37 V (0.09%) | 6.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.18 V (0.04%) | 399.8 V | 0.29 V (0.07%) | 4.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.14 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 4.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.11 V (0.03%) | 399.9 V | 0.18 V (0.05%) | 3.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 2.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.07 V (0.02%) | 399.9 V | 0.11 V (0.03%) | 1.8 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 16 Ampere ved 45 Meter (400V)
Hvilket kabeltværsnit kræves til 16A ved 45 meter (400V)?
Til 16 Ampere over 45 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 10.67V / 2.67%).
Hvor mange kW svarer 16A ved 400V til?
Det svarer til 11.09 kW med en anbefalet sikring på 16A.
Related Lengths & Currents (400V)
16A · 5m (400V)16A · 10m (400V)16A · 15m (400V)16A · 20m (400V)16A · 25m (400V)16A · 30m (400V)16A · 35m (400V)16A · 40m (400V)16A · 50m (400V)16A · 60m (400V)16A · 70m (400V)10A · 45m (400V)20A · 45m (400V)25A · 45m (400V)32A · 45m (400V)40A · 45m (400V)50A · 45m (400V)63A · 45m (400V)80A · 45m (400V)100A · 45m (400V)125A · 45m (400V)160A · 45m (400V)200A · 45m (400V)