Kabeltværsnit for 200 Ampere ved 35 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 200 A over 35 m ved 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 2.73V (0.68%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 3.57V (0.89%)
Voltage at Load397.3 VLine Loss: 946.1 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A172.97 V (43.24%)227.0 V285.33 V (71.33%)59920.0 WDrop High
2.5 mm²24 A18 A103.78 V (25.95%)296.2 V171.2 V (42.8%)35952.0 WDrop High
4 mm²32 A25 A64.87 V (16.22%)335.1 V107.0 V (26.75%)22470.0 WDrop High
6 mm²41 A32 A43.24 V (10.81%)356.8 V71.33 V (17.83%)14980.0 WDrop High
10 mm²57 A44 A25.95 V (6.49%)374.1 V42.8 V (10.7%)8988.0 WDrop High
16 mm²76 A59 A16.22 V (4.05%)383.8 V26.75 V (6.69%)5617.5 WDrop High
25 mm²101 A78 A10.38 V (2.59%)389.6 V17.12 V (4.28%)3595.2 WDrop High
35 mm²125 A97 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2568.0 WDrop High
50 mm²151 A118 A5.19 V (1.3%)394.8 V8.56 V (2.14%)1797.6 WDrop High
70 mm²192 A150 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1284.0 WDrop High
95 mm²232 A181 A2.73 V (0.68%)397.3 V4.51 V (1.13%)946.1 W✓ OK (≤3%)
120 mm²269 A210 A2.16 V (0.54%)397.8 V3.57 V (0.89%)749.0 W✓ OK (≤3%)
150 mm²309 A241 A1.73 V (0.43%)398.3 V2.85 V (0.71%)599.2 W✓ OK (≤3%)
185 mm²353 A275 A1.4 V (0.35%)398.6 V2.31 V (0.58%)485.8 W✓ OK (≤3%)
240 mm²415 A324 A1.08 V (0.27%)398.9 V1.78 V (0.45%)374.5 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (0.22%)399.1 V1.43 V (0.36%)299.6 W✓ OK (≤3%)
400 mm²570 A445 A0.65 V (0.16%)399.4 V1.07 V (0.27%)224.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 200 Ampere ved 35 Meter (400V)

Hvilket kabeltværsnit kræves til 200A ved 35 meter (400V)?

Til 200 Ampere over 35 meter ved 400V anbefales 95 mm² kobberkabel (spændingsfald 2.73V / 0.68%).

Hvor mange kW svarer 200A ved 400V til?

Det svarer til 138.56 kW med en anbefalet sikring på 200A.