Kabeltværsnit for 25 Ampere ved 15 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 25 A over 15 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 3.47V (0.87%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 5.73V (1.43%)
Voltage at Load396.5 VLine Loss: 150.5 W
Max Power & Breaker17.32 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 401.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 240.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 3.47 V (0.87%) | 396.5 V | 5.73 V (1.43%) | 150.5 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 100.3 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.39 V (0.35%) | 398.6 V | 2.29 V (0.57%) | 60.2 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.87 V (0.22%) | 399.1 V | 1.43 V (0.36%) | 37.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.56 V (0.14%) | 399.4 V | 0.92 V (0.23%) | 24.1 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.4 V (0.1%) | 399.6 V | 0.66 V (0.16%) | 17.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 12.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.2 V (0.05%) | 399.8 V | 0.33 V (0.08%) | 8.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.15 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 6.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.12 V (0.03%) | 399.9 V | 0.19 V (0.05%) | 5.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 4.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.08 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 3.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 2.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.05 V (0.01%) | 400.0 V | 0.08 V (0.02%) | 2.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 400.0 V | 0.06 V (0.01%) | 1.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 25 Ampere ved 15 Meter (400V)
Hvilket kabeltværsnit kræves til 25A ved 15 meter (400V)?
Til 25 Ampere over 15 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 3.47V / 0.87%).
Hvor mange kW svarer 25A ved 400V til?
Det svarer til 17.32 kW med en anbefalet sikring på 25A.
Related Lengths & Currents (400V)
25A · 5m (400V)25A · 10m (400V)25A · 20m (400V)25A · 25m (400V)25A · 30m (400V)25A · 35m (400V)25A · 40m (400V)25A · 45m (400V)25A · 50m (400V)25A · 60m (400V)25A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)32A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)125A · 15m (400V)160A · 15m (400V)200A · 15m (400V)