Kabeltværsnit for 63 Ampere ved 70 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 63 A over 70 m ved 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 10.22V (2.55%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.79V (2.7%)
Voltage at Load389.8 VLine Loss: 1114.8 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A108.97 V (27.24%)291.0 V179.76 V (44.94%)11891.1 WDrop High
2.5 mm²24 A18 A65.38 V (16.35%)334.6 V107.85 V (26.96%)7134.7 WDrop High
4 mm²32 A25 A40.87 V (10.22%)359.1 V67.41 V (16.85%)4459.2 WDrop High
6 mm²41 A32 A27.24 V (6.81%)372.8 V44.94 V (11.23%)2972.8 WDrop High
10 mm²57 A44 A16.35 V (4.09%)383.7 V26.96 V (6.74%)1783.7 WDrop High
16 mm²76 A59 A10.22 V (2.55%)389.8 V16.85 V (4.21%)1114.8 W✓ OK (≤3%)
25 mm²101 A78 A6.54 V (1.63%)393.5 V10.79 V (2.7%)713.5 W✓ OK (≤3%)
35 mm²125 A97 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 W✓ OK (≤3%)
50 mm²151 A118 A3.27 V (0.82%)396.7 V5.39 V (1.35%)356.7 W✓ OK (≤3%)
70 mm²192 A150 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
95 mm²232 A181 A1.72 V (0.43%)398.3 V2.84 V (0.71%)187.8 W✓ OK (≤3%)
120 mm²269 A210 A1.36 V (0.34%)398.6 V2.25 V (0.56%)148.6 W✓ OK (≤3%)
150 mm²309 A241 A1.09 V (0.27%)398.9 V1.8 V (0.45%)118.9 W✓ OK (≤3%)
185 mm²353 A275 A0.88 V (0.22%)399.1 V1.46 V (0.36%)96.4 W✓ OK (≤3%)
240 mm²415 A324 A0.68 V (0.17%)399.3 V1.12 V (0.28%)74.3 W✓ OK (≤3%)
300 mm²477 A372 A0.54 V (0.14%)399.5 V0.9 V (0.22%)59.5 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.1%)399.6 V0.67 V (0.17%)44.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 63 Ampere ved 70 Meter (400V)

Hvilket kabeltværsnit kræves til 63A ved 70 meter (400V)?

Til 63 Ampere over 70 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 10.22V / 2.55%).

Hvor mange kW svarer 63A ved 400V til?

Det svarer til 43.65 kW med en anbefalet sikring på 63A.