⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 63 Ampere bei 50 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 63 A über 50 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 7.3V (1.82%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 7.7V (1.93%)
Voltage at Load392.7 VLine Loss: 796.3 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.84 V (19.46%)322.2 V128.4 V (32.1%)8493.7 WDrop High
2.5 mm²24 A18 A46.7 V (11.68%)353.3 V77.04 V (19.26%)5096.2 WDrop High
4 mm²32 A25 A29.19 V (7.3%)370.8 V48.15 V (12.04%)3185.1 WDrop High
6 mm²41 A32 A19.46 V (4.86%)380.5 V32.1 V (8.02%)2123.4 WDrop High
10 mm²57 A44 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 WDrop High
16 mm²76 A59 A7.3 V (1.82%)392.7 V12.04 V (3.01%)796.3 W✓ OK (≤3%)
25 mm²101 A78 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 W✓ OK (≤3%)
35 mm²125 A97 A3.34 V (0.83%)396.7 V5.5 V (1.38%)364.0 W✓ OK (≤3%)
50 mm²151 A118 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
70 mm²192 A150 A1.67 V (0.42%)398.3 V2.75 V (0.69%)182.0 W✓ OK (≤3%)
95 mm²232 A181 A1.23 V (0.31%)398.8 V2.03 V (0.51%)134.1 W✓ OK (≤3%)
120 mm²269 A210 A0.97 V (0.24%)399.0 V1.6 V (0.4%)106.2 W✓ OK (≤3%)
150 mm²309 A241 A0.78 V (0.19%)399.2 V1.28 V (0.32%)84.9 W✓ OK (≤3%)
185 mm²353 A275 A0.63 V (0.16%)399.4 V1.04 V (0.26%)68.9 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)399.5 V0.8 V (0.2%)53.1 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.1%)399.6 V0.64 V (0.16%)42.5 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.07%)399.7 V0.48 V (0.12%)31.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 63 Ampere bei 50 Meter (400V)

Welcher Kabelquerschnitt wird für 63A bei 50m (400V) benötigt?

Für 63 Ampere über 50 Meter bei 400V wird ein Kupferkabel von 16 mm² empfohlen, um den Spannungsfall unter 3% (7.3V bzw. 1.82%) zu halten.

Wie hoch ist die maximale Leistung bei 63A und 400V?

Die übertragbare Leistung beträgt 43.65 kW bei einer empfohlenen Absicherung von 63A.