100 kVA to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 100 kVA on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)120.28 AAt 1.0 PF: 120.28 A
Active / Apparent Power85.0 kW100.0 kVA · 52.68 kVAR
Recommended Breaker160 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire1 AWGIEC Metric: 35 mm²

Engineering Breakdown for 100 kVA at 480V

Input Rating100 kVA (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)120.28 Amps
Amperage at 1.00 Power Factor (Resistive Load)120.28 Amps
Real Power (kW / Watts)85.0 kW (85,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)100.0 kVA / 52.68 kVAR
Equivalent Mechanical Horsepower (HP)113.99 HP
NEC 125% Continuous Circuit Breaker160 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 100 kVA at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 100 kVA equals 120.28 Amps at an industrial power factor of 0.85 (or 120.28 Amps at unity power factor 1.0).

What size breaker and wire is needed for 100 kVA at 480V?

For 120.28A continuous load, NEC requires a 125% rated breaker of 160A with 1 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.