20 kVA to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 20 kVA on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)50.2 AAt 1.0 PF: 50.2 A
Active / Apparent Power17.0 kW20.0 kVA · 10.54 kVAR
Recommended Breaker63 A (NEC)60 A (IEC Nominal)
Recommended Copper Wire6 AWGIEC Metric: 10 mm²

Engineering Breakdown for 20 kVA at 230V

Input Rating20 kVA (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)50.2 Amps
Amperage at 1.00 Power Factor (Resistive Load)50.2 Amps
Real Power (kW / Watts)17.0 kW (17,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)20.0 kVA / 10.54 kVAR
Equivalent Mechanical Horsepower (HP)22.8 HP
NEC 125% Continuous Circuit Breaker63 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)6 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 20 kVA at 230V (3-Phase)?

At 230V Three-Phase AC, 20 kVA equals 50.2 Amps at an industrial power factor of 0.85 (or 50.2 Amps at unity power factor 1.0).

What size breaker and wire is needed for 20 kVA at 230V?

For 50.2A continuous load, NEC requires a 125% rated breaker of 63A with 6 AWG copper conductors, while IEC standard sizing uses a 60A breaker with 10 mm² copper cable.