⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

3 kVA to Amps at 400V Three-Phase AC (IEC Europe)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 3 kVA on a 400V Three-Phase AC (IEC Europe) circuit.

Line Current (0.85 PF)4.33 AAt 1.0 PF: 4.33 A
Active / Apparent Power2.55 kW3.0 kVA · 1.58 kVAR
Recommended Breaker6 A (NEC)6 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 3 kVA at 400V

Input Rating3 kVA (400V Three-Phase AC (IEC Europe))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)4.33 Amps
Amperage at 1.00 Power Factor (Resistive Load)4.33 Amps
Real Power (kW / Watts)2.55 kW (2,550 W)
Apparent Power (kVA) & Reactive Power (kVAR)3.0 kVA / 1.58 kVAR
Equivalent Mechanical Horsepower (HP)3.42 HP
NEC 125% Continuous Circuit Breaker6 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 3 kVA at 400V (3-Phase)?

At 400V Three-Phase AC (IEC Europe), 3 kVA equals 4.33 Amps at an industrial power factor of 0.85 (or 4.33 Amps at unity power factor 1.0).

What size breaker and wire is needed for 3 kVA at 400V?

For 4.33A continuous load, NEC requires a 125% rated breaker of 6A with 14 AWG copper conductors, while IEC standard sizing uses a 6A breaker with 1.5 mm² copper cable.