4.5 kVA to Amps at 208V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 4.5 kVA on a 208V Three-Phase AC circuit.

Line Current (0.85 PF)12.49 AAt 1.0 PF: 12.49 A
Active / Apparent Power3.82 kW4.5 kVA · 2.37 kVAR
Recommended Breaker16 A (NEC)13 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 4.5 kVA at 208V

Input Rating4.5 kVA (208V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)12.49 Amps
Amperage at 1.00 Power Factor (Resistive Load)12.49 Amps
Real Power (kW / Watts)3.82 kW (3,825 W)
Apparent Power (kVA) & Reactive Power (kVAR)4.5 kVA / 2.37 kVAR
Equivalent Mechanical Horsepower (HP)5.13 HP
NEC 125% Continuous Circuit Breaker16 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 4.5 kVA at 208V (3-Phase)?

At 208V Three-Phase AC, 4.5 kVA equals 12.49 Amps at an industrial power factor of 0.85 (or 12.49 Amps at unity power factor 1.0).

What size breaker and wire is needed for 4.5 kVA at 208V?

For 12.49A continuous load, NEC requires a 125% rated breaker of 16A with 14 AWG copper conductors, while IEC standard sizing uses a 13A breaker with 1.5 mm² copper cable.