⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

9 kVA to Amps at 240V Single-Phase AC (NEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 9 kVA on a 240V Single-Phase AC (NEC) circuit.

Line Current (0.85 PF)37.5 AAt 1.0 PF: 37.5 A
Active / Apparent Power7.65 kW9.0 kVA · 4.74 kVAR
Recommended Breaker50 A (NEC)40 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 9 kVA at 240V

Input Rating9 kVA (240V Single-Phase AC (NEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)37.5 Amps
Amperage at 1.00 Power Factor (Resistive Load)37.5 Amps
Real Power (kW / Watts)7.65 kW (7,650 W)
Apparent Power (kVA) & Reactive Power (kVAR)9.0 kVA / 4.74 kVAR
Equivalent Mechanical Horsepower (HP)10.26 HP
NEC 125% Continuous Circuit Breaker50 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 9 kVA at 240V (1-Phase)?

At 240V Single-Phase AC (NEC), 9 kVA equals 37.5 Amps at an industrial power factor of 0.85 (or 37.5 Amps at unity power factor 1.0).

What size breaker and wire is needed for 9 kVA at 240V?

For 37.5A continuous load, NEC requires a 125% rated breaker of 50A with 8 AWG copper conductors, while IEC standard sizing uses a 40A breaker with 10 mm² copper cable.