Kabelarea för 16 Ampere vid 70 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 70 m vid 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 10.38V (2.59%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 11.41V (2.85%)
Voltage at Load389.6 VLine Loss: 287.6 W
Max Power & Breaker11.09 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 27.68 V (6.92%) | 372.3 V | 45.65 V (11.41%) | 767.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 16.61 V (4.15%) | 383.4 V | 27.39 V (6.85%) | 460.2 W | ~ ≤5% |
| 4 mm² | 32 A | 25 A | 10.38 V (2.59%) | 389.6 V | 17.12 V (4.28%) | 287.6 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 6.92 V (1.73%) | 393.1 V | 11.41 V (2.85%) | 191.7 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 4.15 V (1.04%) | 395.8 V | 6.85 V (1.71%) | 115.0 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 2.59 V (0.65%) | 397.4 V | 4.28 V (1.07%) | 71.9 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.66 V (0.42%) | 398.3 V | 2.74 V (0.68%) | 46.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 32.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.83 V (0.21%) | 399.2 V | 1.37 V (0.34%) | 23.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 16.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.44 V (0.11%) | 399.6 V | 0.72 V (0.18%) | 12.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.35 V (0.09%) | 399.7 V | 0.57 V (0.14%) | 9.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 7.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.22 V (0.06%) | 399.8 V | 0.37 V (0.09%) | 6.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.17 V (0.04%) | 399.8 V | 0.29 V (0.07%) | 4.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.14 V (0.03%) | 399.9 V | 0.23 V (0.06%) | 3.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.1 V (0.03%) | 399.9 V | 0.17 V (0.04%) | 2.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 16 Ampere vid 70 Meter (400V)
Vilken kabelarea krävs för 16A vid 70 meter (400V)?
För 16 Ampere över 70 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (10.38V / 2.59%).
Hur stor effekt motsvarar 16A vid 400V?
Det motsvarar 11.09 kW med en rekommenderad säkring på 16A.
Related Lengths & Currents (400V)
16A · 5m (400V)16A · 10m (400V)16A · 15m (400V)16A · 20m (400V)16A · 25m (400V)16A · 30m (400V)16A · 35m (400V)16A · 40m (400V)16A · 45m (400V)16A · 50m (400V)16A · 60m (400V)10A · 70m (400V)20A · 70m (400V)25A · 70m (400V)32A · 70m (400V)40A · 70m (400V)50A · 70m (400V)63A · 70m (400V)80A · 70m (400V)100A · 70m (400V)125A · 70m (400V)160A · 70m (400V)200A · 70m (400V)