Kabelarea för 160 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 30 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 2.54V (0.64%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.09V (0.77%)
Voltage at Load397.5 VLine Loss: 704.4 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A118.61 V (29.65%)281.4 V195.65 V (48.91%)32870.4 WDrop High
2.5 mm²24 A18 A71.17 V (17.79%)328.8 V117.39 V (29.35%)19722.2 WDrop High
4 mm²32 A25 A44.48 V (11.12%)355.5 V73.37 V (18.34%)12326.4 WDrop High
6 mm²41 A32 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
10 mm²57 A44 A17.79 V (4.45%)382.2 V29.35 V (7.34%)4930.6 WDrop High
16 mm²76 A59 A11.12 V (2.78%)388.9 V18.34 V (4.59%)3081.6 WDrop High
25 mm²101 A78 A7.12 V (1.78%)392.9 V11.74 V (2.93%)1972.2 WDrop High
35 mm²125 A97 A5.08 V (1.27%)394.9 V8.39 V (2.1%)1408.7 WDrop High
50 mm²151 A118 A3.56 V (0.89%)396.4 V5.87 V (1.47%)986.1 WDrop High
70 mm²192 A150 A2.54 V (0.64%)397.5 V4.19 V (1.05%)704.4 W✓ OK (≤3%)
95 mm²232 A181 A1.87 V (0.47%)398.1 V3.09 V (0.77%)519.0 W✓ OK (≤3%)
120 mm²269 A210 A1.48 V (0.37%)398.5 V2.45 V (0.61%)410.9 W✓ OK (≤3%)
150 mm²309 A241 A1.19 V (0.3%)398.8 V1.96 V (0.49%)328.7 W✓ OK (≤3%)
185 mm²353 A275 A0.96 V (0.24%)399.0 V1.59 V (0.4%)266.5 W✓ OK (≤3%)
240 mm²415 A324 A0.74 V (0.19%)399.3 V1.22 V (0.31%)205.4 W✓ OK (≤3%)
300 mm²477 A372 A0.59 V (0.15%)399.4 V0.98 V (0.24%)164.4 W✓ OK (≤3%)
400 mm²570 A445 A0.44 V (0.11%)399.6 V0.73 V (0.18%)123.3 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 160A vid 30 meter (400V)?

För 160 Ampere över 30 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (2.54V / 0.64%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.