⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.08%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.18V (2.16%)
Voltage at Load End235.0 VLoss: 4.99 V (199.5 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.07 V (8.36%)219.9 V33.11 V (13.79%)802.8 WDrop/Amp High
12 AWG3.31 mm²20 A12.61 V (5.25%)227.4 V20.8 V (8.67%)504.5 WDrop/Amp High
10 AWG5.26 mm²30 A7.94 V (3.31%)232.1 V13.09 V (5.45%)317.5 WDrop/Amp High
8 AWG8.37 mm²50 A4.99 V (2.08%)235.0 V8.23 V (3.43%)199.5 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.14 V (1.31%)236.9 V5.18 V (2.16%)125.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.97 V (0.82%)238.0 V3.26 V (1.36%)79.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.57 V (0.65%)238.4 V2.58 V (1.08%)62.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.24 V (0.52%)238.8 V2.05 V (0.85%)49.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.98 V (0.41%)239.0 V1.62 V (0.68%)39.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.78 V (0.33%)239.2 V1.29 V (0.54%)31.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.62 V (0.26%)239.4 V1.02 V (0.43%)24.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.49 V (0.2%)239.5 V0.81 V (0.34%)19.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.39 V (0.16%)239.6 V0.64 V (0.27%)15.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.33 V (0.14%)239.7 V0.54 V (0.23%)13.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.11%)239.7 V0.45 V (0.19%)11.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (0.1%)239.8 V0.39 V (0.16%)9.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (0.09%)239.8 V0.34 V (0.14%)8.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.07%)239.8 V0.27 V (0.11%)6.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.06%)239.9 V0.23 V (0.09%)5.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.05%)239.9 V0.18 V (0.08%)4.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.14 V (0.06%)3.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 80 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.99V (2.08%) and delivers 235.0V at the load.

What size aluminum wire is required for 40 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.18V (2.16%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.