🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 50 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.62%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.04V (1.69%)
Voltage at Load End236.1 VLoss: 3.9 V (194.8 W)
Power & Breaker (125%)12.0 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A15.68 V (6.53%)224.3 V25.86 V (10.78%)784.0 WDrop/Amp High
12 AWG3.31 mm²20 A9.85 V (4.11%)230.1 V16.25 V (6.77%)492.7 WDrop/Amp High
10 AWG5.26 mm²30 A6.2 V (2.58%)233.8 V10.23 V (4.26%)310.0 WDrop/Amp High
8 AWG8.37 mm²50 A3.9 V (1.62%)236.1 V6.43 V (2.68%)194.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.45 V (1.02%)237.5 V4.04 V (1.69%)122.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.54 V (0.64%)238.5 V2.54 V (1.06%)77.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.22 V (0.51%)238.8 V2.02 V (0.84%)61.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.97 V (0.4%)239.0 V1.6 V (0.67%)48.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.77 V (0.32%)239.2 V1.27 V (0.53%)38.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.61 V (0.25%)239.4 V1.01 V (0.42%)30.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.48 V (0.2%)239.5 V0.8 V (0.33%)24.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.38 V (0.16%)239.6 V0.63 V (0.26%)19.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.3 V (0.13%)239.7 V0.5 V (0.21%)15.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.26 V (0.11%)239.7 V0.42 V (0.18%)12.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.21 V (0.09%)239.8 V0.35 V (0.15%)10.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.08%)239.8 V0.3 V (0.13%)9.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.16 V (0.07%)239.8 V0.27 V (0.11%)8.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.13 V (0.05%)239.9 V0.21 V (0.09%)6.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.11 V (0.04%)239.9 V0.18 V (0.07%)5.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.04%)239.9 V0.14 V (0.06%)4.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.03%)239.9 V0.11 V (0.04%)3.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 50 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.9V (1.62%) and delivers 236.1V at the load.

What size aluminum wire is required for 50 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.04V (1.69%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.