5 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 3.71V (0.93%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 6.11V (1.53%)
Voltage at Load396.3 VLine Loss: 32.1 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.71 V (0.93%)396.3 V6.11 V (1.53%)32.1 W✓ OK (≤3%)
2.5 mm²24 A18 A2.22 V (0.56%)397.8 V3.67 V (0.92%)19.3 W✓ OK (≤3%)
4 mm²32 A25 A1.39 V (0.35%)398.6 V2.29 V (0.57%)12.0 W✓ OK (≤3%)
6 mm²41 A32 A0.93 V (0.23%)399.1 V1.53 V (0.38%)8.0 W✓ OK (≤3%)
10 mm²57 A44 A0.56 V (0.14%)399.4 V0.92 V (0.23%)4.8 W✓ OK (≤3%)
16 mm²76 A59 A0.35 V (0.09%)399.7 V0.57 V (0.14%)3.0 W✓ OK (≤3%)
25 mm²101 A78 A0.22 V (0.06%)399.8 V0.37 V (0.09%)1.9 W✓ OK (≤3%)
35 mm²125 A97 A0.16 V (0.04%)399.8 V0.26 V (0.07%)1.4 W✓ OK (≤3%)
50 mm²151 A118 A0.11 V (0.03%)399.9 V0.18 V (0.05%)1.0 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.02%)399.9 V0.13 V (0.03%)0.7 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.01%)399.9 V0.1 V (0.02%)0.5 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.01%)400.0 V0.08 V (0.02%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.01%)400.0 V0.06 V (0.02%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 5A at 30 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 5A over 30m at 400V (voltage drop: 3.71V or 0.93%).

What is the power capacity of 5A at 400V?

At unity power factor, 5A at 400V supports 3.46 kW with a standard 6A circuit breaker.