Kabelquerschnitt für 50 Ampere bei 30 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 50 A über 30 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.56V (1.39%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.73V (1.43%)
Voltage at Load394.4 VLine Loss: 481.5 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)3210.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1926.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)1203.8 WDrop High
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)802.5 WDrop High
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)481.5 W✓ OK (≤3%)
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)300.9 W✓ OK (≤3%)
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)192.6 W✓ OK (≤3%)
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)137.6 W✓ OK (≤3%)
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)96.3 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)68.8 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)50.7 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)40.1 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)32.1 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)26.0 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)20.1 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)16.1 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)12.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 50 Ampere bei 30 Meter (400V)

Welcher Kabelquerschnitt wird für 50A bei 30m (400V) benötigt?

Für 50 Ampere über 30 Meter bei 400V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (5.56V bzw. 1.39%) zu halten.

Wie hoch ist die maximale Leistung bei 50A und 400V?

Die übertragbare Leistung beträgt 34.64 kW bei einer empfohlenen Absicherung von 50A.