Kabelquerschnitt für 50 Ampere bei 70 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 50 A über 70 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 8.11V (2.03%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 8.56V (2.14%)
Voltage at Load391.9 VLine Loss: 702.2 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A86.49 V (21.62%)313.5 V142.66 V (35.67%)7490.0 WDrop High
2.5 mm²24 A18 A51.89 V (12.97%)348.1 V85.6 V (21.4%)4494.0 WDrop High
4 mm²32 A25 A32.43 V (8.11%)367.6 V53.5 V (13.37%)2808.8 WDrop High
6 mm²41 A32 A21.62 V (5.41%)378.4 V35.67 V (8.92%)1872.5 WDrop High
10 mm²57 A44 A12.97 V (3.24%)387.0 V21.4 V (5.35%)1123.5 W~ ≤5%
16 mm²76 A59 A8.11 V (2.03%)391.9 V13.37 V (3.34%)702.2 W✓ OK (≤3%)
25 mm²101 A78 A5.19 V (1.3%)394.8 V8.56 V (2.14%)449.4 W✓ OK (≤3%)
35 mm²125 A97 A3.71 V (0.93%)396.3 V6.11 V (1.53%)321.0 W✓ OK (≤3%)
50 mm²151 A118 A2.59 V (0.65%)397.4 V4.28 V (1.07%)224.7 W✓ OK (≤3%)
70 mm²192 A150 A1.85 V (0.46%)398.1 V3.06 V (0.76%)160.5 W✓ OK (≤3%)
95 mm²232 A181 A1.37 V (0.34%)398.6 V2.25 V (0.56%)118.3 W✓ OK (≤3%)
120 mm²269 A210 A1.08 V (0.27%)398.9 V1.78 V (0.45%)93.6 W✓ OK (≤3%)
150 mm²309 A241 A0.86 V (0.22%)399.1 V1.43 V (0.36%)74.9 W✓ OK (≤3%)
185 mm²353 A275 A0.7 V (0.18%)399.3 V1.16 V (0.29%)60.7 W✓ OK (≤3%)
240 mm²415 A324 A0.54 V (0.14%)399.5 V0.89 V (0.22%)46.8 W✓ OK (≤3%)
300 mm²477 A372 A0.43 V (0.11%)399.6 V0.71 V (0.18%)37.4 W✓ OK (≤3%)
400 mm²570 A445 A0.32 V (0.08%)399.7 V0.53 V (0.13%)28.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 50 Ampere bei 70 Meter (400V)

Welcher Kabelquerschnitt wird für 50A bei 70m (400V) benötigt?

Für 50 Ampere über 70 Meter bei 400V wird ein Kupferkabel von 16 mm² empfohlen, um den Spannungsfall unter 3% (8.11V bzw. 2.03%) zu halten.

Wie hoch ist die maximale Leistung bei 50A und 400V?

Die übertragbare Leistung beträgt 34.64 kW bei einer empfohlenen Absicherung von 50A.