⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 200 Ampere bei 70 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 200 A über 70 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.46V (1.37%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 7.13V (1.78%)
Voltage at Load394.5 VLine Loss: 1892.2 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (86.49%)54.1 V570.65 V (142.66%)119840.0 WDrop High
2.5 mm²24 A18 A207.57 V (51.89%)192.4 V342.39 V (85.6%)71904.0 WDrop High
4 mm²32 A25 A129.73 V (32.43%)270.3 V213.99 V (53.5%)44940.0 WDrop High
6 mm²41 A32 A86.49 V (21.62%)313.5 V142.66 V (35.67%)29960.0 WDrop High
10 mm²57 A44 A51.89 V (12.97%)348.1 V85.6 V (21.4%)17976.0 WDrop High
16 mm²76 A59 A32.43 V (8.11%)367.6 V53.5 V (13.37%)11235.0 WDrop High
25 mm²101 A78 A20.76 V (5.19%)379.2 V34.24 V (8.56%)7190.4 WDrop High
35 mm²125 A97 A14.83 V (3.71%)385.2 V24.46 V (6.11%)5136.0 WDrop High
50 mm²151 A118 A10.38 V (2.59%)389.6 V17.12 V (4.28%)3595.2 WDrop High
70 mm²192 A150 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2568.0 WDrop High
95 mm²232 A181 A5.46 V (1.37%)394.5 V9.01 V (2.25%)1892.2 W✓ OK (≤3%)
120 mm²269 A210 A4.32 V (1.08%)395.7 V7.13 V (1.78%)1498.0 W✓ OK (≤3%)
150 mm²309 A241 A3.46 V (0.86%)396.5 V5.71 V (1.43%)1198.4 W✓ OK (≤3%)
185 mm²353 A275 A2.8 V (0.7%)397.2 V4.63 V (1.16%)971.7 W✓ OK (≤3%)
240 mm²415 A324 A2.16 V (0.54%)397.8 V3.57 V (0.89%)749.0 W✓ OK (≤3%)
300 mm²477 A372 A1.73 V (0.43%)398.3 V2.85 V (0.71%)599.2 W✓ OK (≤3%)
400 mm²570 A445 A1.3 V (0.32%)398.7 V2.14 V (0.53%)449.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 200 Ampere bei 70 Meter (400V)

Welcher Kabelquerschnitt wird für 200A bei 70m (400V) benötigt?

Für 200 Ampere über 70 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (5.46V bzw. 1.37%) zu halten.

Wie hoch ist die maximale Leistung bei 200A und 400V?

Die übertragbare Leistung beträgt 138.56 kW bei einer empfohlenen Absicherung von 200A.