Kabelquerschnitt für 200 Ampere bei 5 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 200 A über 5 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 0.39V (0.1%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.51V (0.13%)
Voltage at Load399.6 VLine Loss: 135.2 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.71 V (6.18%)375.3 V40.76 V (10.19%)8560.0 WDrop High
2.5 mm²24 A18 A14.83 V (3.71%)385.2 V24.46 V (6.11%)5136.0 WDrop High
4 mm²32 A25 A9.27 V (2.32%)390.7 V15.29 V (3.82%)3210.0 WDrop High
6 mm²41 A32 A6.18 V (1.54%)393.8 V10.19 V (2.55%)2140.0 WDrop High
10 mm²57 A44 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1284.0 WDrop High
16 mm²76 A59 A2.32 V (0.58%)397.7 V3.82 V (0.96%)802.5 WDrop High
25 mm²101 A78 A1.48 V (0.37%)398.5 V2.45 V (0.61%)513.6 WDrop High
35 mm²125 A97 A1.06 V (0.26%)398.9 V1.75 V (0.44%)366.9 WDrop High
50 mm²151 A118 A0.74 V (0.19%)399.3 V1.22 V (0.31%)256.8 WDrop High
70 mm²192 A150 A0.53 V (0.13%)399.5 V0.87 V (0.22%)183.4 WDrop High
95 mm²232 A181 A0.39 V (0.1%)399.6 V0.64 V (0.16%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.08%)399.7 V0.51 V (0.13%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.06%)399.8 V0.41 V (0.1%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.05%)399.8 V0.33 V (0.08%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)399.8 V0.25 V (0.06%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)399.9 V0.2 V (0.05%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)399.9 V0.15 V (0.04%)32.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 200 Ampere bei 5 Meter (400V)

Welcher Kabelquerschnitt wird für 200A bei 5m (400V) benötigt?

Für 200 Ampere über 5 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (0.39V bzw. 0.1%) zu halten.

Wie hoch ist die maximale Leistung bei 200A und 400V?

Die übertragbare Leistung beträgt 138.56 kW bei einer empfohlenen Absicherung von 200A.