Kabelquerschnitt für 25 Ampere bei 5 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 5 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 1.16V (0.29%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 1.91V (0.48%)
Voltage at Load398.8 VLine Loss: 50.2 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.09 V (0.77%)396.9 V5.1 V (1.27%)133.8 WDrop High
2.5 mm²24 A18 A1.85 V (0.46%)398.1 V3.06 V (0.76%)80.2 WDrop High
4 mm²32 A25 A1.16 V (0.29%)398.8 V1.91 V (0.48%)50.2 W✓ OK (≤3%)
6 mm²41 A32 A0.77 V (0.19%)399.2 V1.27 V (0.32%)33.4 W✓ OK (≤3%)
10 mm²57 A44 A0.46 V (0.12%)399.5 V0.76 V (0.19%)20.1 W✓ OK (≤3%)
16 mm²76 A59 A0.29 V (0.07%)399.7 V0.48 V (0.12%)12.5 W✓ OK (≤3%)
25 mm²101 A78 A0.19 V (0.05%)399.8 V0.31 V (0.08%)8.0 W✓ OK (≤3%)
35 mm²125 A97 A0.13 V (0.03%)399.9 V0.22 V (0.05%)5.7 W✓ OK (≤3%)
50 mm²151 A118 A0.09 V (0.02%)399.9 V0.15 V (0.04%)4.0 W✓ OK (≤3%)
70 mm²192 A150 A0.07 V (0.02%)399.9 V0.11 V (0.03%)2.9 W✓ OK (≤3%)
95 mm²232 A181 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.1 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.7 W✓ OK (≤3%)
150 mm²309 A241 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.3 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.04 V (0.01%)1.1 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.8 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.0%)0.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 5 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 5m (400V) benötigt?

Für 25 Ampere über 5 Meter bei 400V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (1.16V bzw. 0.29%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.