Kabelquerschnitt für 80 Ampere bei 5 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 80 A über 5 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 0.59V (0.15%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.7V (0.17%)
Voltage at Load399.4 VLine Loss: 82.2 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.88 V (2.47%)390.1 V16.3 V (4.08%)1369.6 WDrop High
2.5 mm²24 A18 A5.93 V (1.48%)394.1 V9.78 V (2.45%)821.8 WDrop High
4 mm²32 A25 A3.71 V (0.93%)396.3 V6.11 V (1.53%)513.6 WDrop High
6 mm²41 A32 A2.47 V (0.62%)397.5 V4.08 V (1.02%)342.4 WDrop High
10 mm²57 A44 A1.48 V (0.37%)398.5 V2.45 V (0.61%)205.4 WDrop High
16 mm²76 A59 A0.93 V (0.23%)399.1 V1.53 V (0.38%)128.4 WDrop High
25 mm²101 A78 A0.59 V (0.15%)399.4 V0.98 V (0.24%)82.2 W✓ OK (≤3%)
35 mm²125 A97 A0.42 V (0.11%)399.6 V0.7 V (0.17%)58.7 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.07%)399.7 V0.49 V (0.12%)41.1 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.05%)399.8 V0.35 V (0.09%)29.3 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.04%)399.8 V0.26 V (0.06%)21.6 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.03%)399.9 V0.2 V (0.05%)17.1 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.02%)399.9 V0.16 V (0.04%)13.7 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.02%)399.9 V0.13 V (0.03%)11.1 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.02%)399.9 V0.1 V (0.03%)8.6 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)400.0 V0.08 V (0.02%)6.8 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.06 V (0.02%)5.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 80 Ampere bei 5 Meter (400V)

Welcher Kabelquerschnitt wird für 80A bei 5m (400V) benötigt?

Für 80 Ampere über 5 Meter bei 400V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (0.59V bzw. 0.15%) zu halten.

Wie hoch ist die maximale Leistung bei 80A und 400V?

Die übertragbare Leistung beträgt 55.43 kW bei einer empfohlenen Absicherung von 80A.