Kabelquerschnitt für 200 Ampere bei 40 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 200 A über 40 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 3.12V (0.78%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 4.08V (1.02%)
Voltage at Load396.9 VLine Loss: 1081.3 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A197.68 V (49.42%)202.3 V326.09 V (81.52%)68480.0 WDrop High
2.5 mm²24 A18 A118.61 V (29.65%)281.4 V195.65 V (48.91%)41088.0 WDrop High
4 mm²32 A25 A74.13 V (18.53%)325.9 V122.28 V (30.57%)25680.0 WDrop High
6 mm²41 A32 A49.42 V (12.36%)350.6 V81.52 V (20.38%)17120.0 WDrop High
10 mm²57 A44 A29.65 V (7.41%)370.3 V48.91 V (12.23%)10272.0 WDrop High
16 mm²76 A59 A18.53 V (4.63%)381.5 V30.57 V (7.64%)6420.0 WDrop High
25 mm²101 A78 A11.86 V (2.97%)388.1 V19.57 V (4.89%)4108.8 WDrop High
35 mm²125 A97 A8.47 V (2.12%)391.5 V13.98 V (3.49%)2934.9 WDrop High
50 mm²151 A118 A5.93 V (1.48%)394.1 V9.78 V (2.45%)2054.4 WDrop High
70 mm²192 A150 A4.24 V (1.06%)395.8 V6.99 V (1.75%)1467.4 WDrop High
95 mm²232 A181 A3.12 V (0.78%)396.9 V5.15 V (1.29%)1081.3 W✓ OK (≤3%)
120 mm²269 A210 A2.47 V (0.62%)397.5 V4.08 V (1.02%)856.0 W✓ OK (≤3%)
150 mm²309 A241 A1.98 V (0.49%)398.0 V3.26 V (0.82%)684.8 W✓ OK (≤3%)
185 mm²353 A275 A1.6 V (0.4%)398.4 V2.64 V (0.66%)555.2 W✓ OK (≤3%)
240 mm²415 A324 A1.24 V (0.31%)398.8 V2.04 V (0.51%)428.0 W✓ OK (≤3%)
300 mm²477 A372 A0.99 V (0.25%)399.0 V1.63 V (0.41%)342.4 W✓ OK (≤3%)
400 mm²570 A445 A0.74 V (0.19%)399.3 V1.22 V (0.31%)256.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 200 Ampere bei 40 Meter (400V)

Welcher Kabelquerschnitt wird für 200A bei 40m (400V) benötigt?

Für 200 Ampere über 40 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (3.12V bzw. 0.78%) zu halten.

Wie hoch ist die maximale Leistung bei 200A und 400V?

Die übertragbare Leistung beträgt 138.56 kW bei einer empfohlenen Absicherung von 200A.