⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

17.5 kVA to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 17.5 kVA on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)21.05 AAt 1.0 PF: 21.05 A
Active / Apparent Power14.88 kW17.5 kVA · 9.22 kVAR
Recommended Breaker30 A (NEC)25 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 2.5 mm²

Engineering Breakdown for 17.5 kVA at 480V

Input Rating17.5 kVA (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)21.05 Amps
Amperage at 1.00 Power Factor (Resistive Load)21.05 Amps
Real Power (kW / Watts)14.88 kW (14,875 W)
Apparent Power (kVA) & Reactive Power (kVAR)17.5 kVA / 9.22 kVAR
Equivalent Mechanical Horsepower (HP)19.95 HP
NEC 125% Continuous Circuit Breaker30 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 2.5 mm² (IEC)

Frequently Asked Questions

How many amps is 17.5 kVA at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 17.5 kVA equals 21.05 Amps at an industrial power factor of 0.85 (or 21.05 Amps at unity power factor 1.0).

What size breaker and wire is needed for 17.5 kVA at 480V?

For 21.05A continuous load, NEC requires a 125% rated breaker of 30A with 10 AWG copper conductors, while IEC standard sizing uses a 25A breaker with 2.5 mm² copper cable.