18.5 kVA to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 18.5 kVA on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)46.44 AAt 1.0 PF: 46.44 A
Active / Apparent Power15.72 kW18.5 kVA · 9.75 kVAR
Recommended Breaker60 A (NEC)50 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 18.5 kVA at 230V

Input Rating18.5 kVA (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)46.44 Amps
Amperage at 1.00 Power Factor (Resistive Load)46.44 Amps
Real Power (kW / Watts)15.72 kW (15,725 W)
Apparent Power (kVA) & Reactive Power (kVAR)18.5 kVA / 9.75 kVAR
Equivalent Mechanical Horsepower (HP)21.09 HP
NEC 125% Continuous Circuit Breaker60 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 18.5 kVA at 230V (3-Phase)?

At 230V Three-Phase AC, 18.5 kVA equals 46.44 Amps at an industrial power factor of 0.85 (or 46.44 Amps at unity power factor 1.0).

What size breaker and wire is needed for 18.5 kVA at 230V?

For 46.44A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 50A breaker with 10 mm² copper cable.