⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 200 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 10 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 0.78V (0.2%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.02V (0.25%)
Voltage at Load399.2 VLine Loss: 270.3 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (12.36%)350.6 V81.52 V (20.38%)17120.0 WDrop High
2.5 mm²24 A18 A29.65 V (7.41%)370.3 V48.91 V (12.23%)10272.0 WDrop High
4 mm²32 A25 A18.53 V (4.63%)381.5 V30.57 V (7.64%)6420.0 WDrop High
6 mm²41 A32 A12.36 V (3.09%)387.6 V20.38 V (5.1%)4280.0 WDrop High
10 mm²57 A44 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2568.0 WDrop High
16 mm²76 A59 A4.63 V (1.16%)395.4 V7.64 V (1.91%)1605.0 WDrop High
25 mm²101 A78 A2.97 V (0.74%)397.0 V4.89 V (1.22%)1027.2 WDrop High
35 mm²125 A97 A2.12 V (0.53%)397.9 V3.49 V (0.87%)733.7 WDrop High
50 mm²151 A118 A1.48 V (0.37%)398.5 V2.45 V (0.61%)513.6 WDrop High
70 mm²192 A150 A1.06 V (0.26%)398.9 V1.75 V (0.44%)366.9 WDrop High
95 mm²232 A181 A0.78 V (0.2%)399.2 V1.29 V (0.32%)270.3 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (0.15%)399.4 V1.02 V (0.25%)214.0 W✓ OK (≤3%)
150 mm²309 A241 A0.49 V (0.12%)399.5 V0.82 V (0.2%)171.2 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.1%)399.6 V0.66 V (0.17%)138.8 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.08%)399.7 V0.51 V (0.13%)107.0 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.06%)399.8 V0.41 V (0.1%)85.6 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.05%)399.8 V0.31 V (0.08%)64.2 W✓ OK (≤3%)

FAQ — Kabelarea för 200 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 200A vid 10 meter (400V)?

För 200 Ampere över 10 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (0.78V / 0.2%).

Hur stor effekt motsvarar 200A vid 400V?

Det motsvarar 138.56 kW med en rekommenderad säkring på 200A.