Kabelarea för 25 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 25 A över 10 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 2.32V (0.58%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 3.82V (0.96%)
Voltage at Load397.7 VLine Loss: 100.3 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.18 V (1.54%)393.8 V10.19 V (2.55%)267.5 WDrop High
2.5 mm²24 A18 A3.71 V (0.93%)396.3 V6.11 V (1.53%)160.5 WDrop High
4 mm²32 A25 A2.32 V (0.58%)397.7 V3.82 V (0.96%)100.3 W✓ OK (≤3%)
6 mm²41 A32 A1.54 V (0.39%)398.5 V2.55 V (0.64%)66.9 W✓ OK (≤3%)
10 mm²57 A44 A0.93 V (0.23%)399.1 V1.53 V (0.38%)40.1 W✓ OK (≤3%)
16 mm²76 A59 A0.58 V (0.14%)399.4 V0.96 V (0.24%)25.1 W✓ OK (≤3%)
25 mm²101 A78 A0.37 V (0.09%)399.6 V0.61 V (0.15%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A0.26 V (0.07%)399.7 V0.44 V (0.11%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.19 V (0.05%)399.8 V0.31 V (0.08%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.13 V (0.03%)399.9 V0.22 V (0.05%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.1 V (0.02%)399.9 V0.16 V (0.04%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.08 V (0.02%)399.9 V0.13 V (0.03%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.02%)399.9 V0.1 V (0.03%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)399.9 V0.08 V (0.02%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)400.0 V0.04 V (0.01%)1.0 W✓ OK (≤3%)

FAQ — Kabelarea för 25 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 25A vid 10 meter (400V)?

För 25 Ampere över 10 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (2.32V / 0.58%).

Hur stor effekt motsvarar 25A vid 400V?

Det motsvarar 17.32 kW med en rekommenderad säkring på 25A.