Kabelarea för 25 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 25 A över 60 m vid 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.17V (2.29%)
Voltage at Load390.7 VLine Loss: 401.2 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)1605.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)963.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)601.9 W~ ≤5%
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)401.2 W✓ OK (≤3%)
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)240.8 W✓ OK (≤3%)
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)150.5 W✓ OK (≤3%)
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)96.3 W✓ OK (≤3%)
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)68.8 W✓ OK (≤3%)
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)48.2 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)34.4 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)25.3 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)20.1 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)16.1 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)13.0 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)10.0 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)8.0 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)6.0 W✓ OK (≤3%)

FAQ — Kabelarea för 25 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 25A vid 60 meter (400V)?

För 25 Ampere över 60 meter vid 400V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 25A vid 400V?

Det motsvarar 17.32 kW med en rekommenderad säkring på 25A.