Kabelarea för 50 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 60 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 11.46V (2.87%)
Voltage at Load388.9 VLine Loss: 963.0 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.13 V (18.53%)325.9 V122.28 V (30.57%)6420.0 WDrop High
2.5 mm²24 A18 A44.48 V (11.12%)355.5 V73.37 V (18.34%)3852.0 WDrop High
4 mm²32 A25 A27.8 V (6.95%)372.2 V45.86 V (11.46%)2407.5 WDrop High
6 mm²41 A32 A18.53 V (4.63%)381.5 V30.57 V (7.64%)1605.0 WDrop High
10 mm²57 A44 A11.12 V (2.78%)388.9 V18.34 V (4.59%)963.0 W✓ OK (≤3%)
16 mm²76 A59 A6.95 V (1.74%)393.1 V11.46 V (2.87%)601.9 W✓ OK (≤3%)
25 mm²101 A78 A4.45 V (1.11%)395.6 V7.34 V (1.83%)385.2 W✓ OK (≤3%)
35 mm²125 A97 A3.18 V (0.79%)396.8 V5.24 V (1.31%)275.1 W✓ OK (≤3%)
50 mm²151 A118 A2.22 V (0.56%)397.8 V3.67 V (0.92%)192.6 W✓ OK (≤3%)
70 mm²192 A150 A1.59 V (0.4%)398.4 V2.62 V (0.66%)137.6 W✓ OK (≤3%)
95 mm²232 A181 A1.17 V (0.29%)398.8 V1.93 V (0.48%)101.4 W✓ OK (≤3%)
120 mm²269 A210 A0.93 V (0.23%)399.1 V1.53 V (0.38%)80.2 W✓ OK (≤3%)
150 mm²309 A241 A0.74 V (0.19%)399.3 V1.22 V (0.31%)64.2 W✓ OK (≤3%)
185 mm²353 A275 A0.6 V (0.15%)399.4 V0.99 V (0.25%)52.1 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (0.12%)399.5 V0.76 V (0.19%)40.1 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.09%)399.6 V0.61 V (0.15%)32.1 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.07%)399.7 V0.46 V (0.11%)24.1 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 50A vid 60 meter (400V)?

För 50 Ampere över 60 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 50A vid 400V?

Det motsvarar 34.64 kW med en rekommenderad säkring på 50A.