Kabelarea för 50 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 50 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.55V (2.39%)
Voltage at Load390.7 VLine Loss: 802.5 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (15.44%)338.2 V101.9 V (25.48%)5350.0 WDrop High
2.5 mm²24 A18 A37.07 V (9.27%)362.9 V61.14 V (15.29%)3210.0 WDrop High
4 mm²32 A25 A23.17 V (5.79%)376.8 V38.21 V (9.55%)2006.2 WDrop High
6 mm²41 A32 A15.44 V (3.86%)384.6 V25.48 V (6.37%)1337.5 WDrop High
10 mm²57 A44 A9.27 V (2.32%)390.7 V15.29 V (3.82%)802.5 W✓ OK (≤3%)
16 mm²76 A59 A5.79 V (1.45%)394.2 V9.55 V (2.39%)501.6 W✓ OK (≤3%)
25 mm²101 A78 A3.71 V (0.93%)396.3 V6.11 V (1.53%)321.0 W✓ OK (≤3%)
35 mm²125 A97 A2.65 V (0.66%)397.4 V4.37 V (1.09%)229.3 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.46%)398.1 V3.06 V (0.76%)160.5 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.33%)398.7 V2.18 V (0.55%)114.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.24%)399.0 V1.61 V (0.4%)84.5 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.19%)399.2 V1.27 V (0.32%)66.9 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)399.4 V1.02 V (0.25%)53.5 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.13%)399.5 V0.83 V (0.21%)43.4 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.1%)399.6 V0.64 V (0.16%)33.4 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.08%)399.7 V0.51 V (0.13%)26.7 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.38 V (0.1%)20.1 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 50A vid 50 meter (400V)?

För 50 Ampere över 50 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 50A vid 400V?

Det motsvarar 34.64 kW med en rekommenderad säkring på 50A.