Kabelarea för 50 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 15 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 2.87V (0.72%)
Voltage at Load397.2 VLine Loss: 240.8 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (4.63%)381.5 V30.57 V (7.64%)1605.0 WDrop High
2.5 mm²24 A18 A11.12 V (2.78%)388.9 V18.34 V (4.59%)963.0 WDrop High
4 mm²32 A25 A6.95 V (1.74%)393.1 V11.46 V (2.87%)601.9 WDrop High
6 mm²41 A32 A4.63 V (1.16%)395.4 V7.64 V (1.91%)401.2 WDrop High
10 mm²57 A44 A2.78 V (0.69%)397.2 V4.59 V (1.15%)240.8 W✓ OK (≤3%)
16 mm²76 A59 A1.74 V (0.43%)398.3 V2.87 V (0.72%)150.5 W✓ OK (≤3%)
25 mm²101 A78 A1.11 V (0.28%)398.9 V1.83 V (0.46%)96.3 W✓ OK (≤3%)
35 mm²125 A97 A0.79 V (0.2%)399.2 V1.31 V (0.33%)68.8 W✓ OK (≤3%)
50 mm²151 A118 A0.56 V (0.14%)399.4 V0.92 V (0.23%)48.2 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.1%)399.6 V0.66 V (0.16%)34.4 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.07%)399.7 V0.48 V (0.12%)25.3 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.06%)399.8 V0.38 V (0.1%)20.1 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.05%)399.8 V0.31 V (0.08%)16.1 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.04%)399.8 V0.25 V (0.06%)13.0 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)399.9 V0.19 V (0.05%)10.0 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)399.9 V0.15 V (0.04%)8.0 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.11 V (0.03%)6.0 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 50A vid 15 meter (400V)?

För 50 Ampere över 15 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (2.78V / 0.69%).

Hur stor effekt motsvarar 50A vid 400V?

Det motsvarar 34.64 kW med en rekommenderad säkring på 50A.