⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 32 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 35 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 10.38V (2.59%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 11.41V (2.85%)
Voltage at Load389.6 VLine Loss: 575.2 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A27.68 V (6.92%)372.3 V45.65 V (11.41%)1534.0 WDrop High
2.5 mm²24 A18 A16.61 V (4.15%)383.4 V27.39 V (6.85%)920.4 WDrop High
4 mm²32 A25 A10.38 V (2.59%)389.6 V17.12 V (4.28%)575.2 W✓ OK (≤3%)
6 mm²41 A32 A6.92 V (1.73%)393.1 V11.41 V (2.85%)383.5 W✓ OK (≤3%)
10 mm²57 A44 A4.15 V (1.04%)395.8 V6.85 V (1.71%)230.1 W✓ OK (≤3%)
16 mm²76 A59 A2.59 V (0.65%)397.4 V4.28 V (1.07%)143.8 W✓ OK (≤3%)
25 mm²101 A78 A1.66 V (0.42%)398.3 V2.74 V (0.68%)92.0 W✓ OK (≤3%)
35 mm²125 A97 A1.19 V (0.3%)398.8 V1.96 V (0.49%)65.7 W✓ OK (≤3%)
50 mm²151 A118 A0.83 V (0.21%)399.2 V1.37 V (0.34%)46.0 W✓ OK (≤3%)
70 mm²192 A150 A0.59 V (0.15%)399.4 V0.98 V (0.24%)32.9 W✓ OK (≤3%)
95 mm²232 A181 A0.44 V (0.11%)399.6 V0.72 V (0.18%)24.2 W✓ OK (≤3%)
120 mm²269 A210 A0.35 V (0.09%)399.7 V0.57 V (0.14%)19.2 W✓ OK (≤3%)
150 mm²309 A241 A0.28 V (0.07%)399.7 V0.46 V (0.11%)15.3 W✓ OK (≤3%)
185 mm²353 A275 A0.22 V (0.06%)399.8 V0.37 V (0.09%)12.4 W✓ OK (≤3%)
240 mm²415 A324 A0.17 V (0.04%)399.8 V0.29 V (0.07%)9.6 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.03%)399.9 V0.23 V (0.06%)7.7 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.03%)399.9 V0.17 V (0.04%)5.8 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 32A vid 35 meter (400V)?

För 32 Ampere över 35 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (10.38V / 2.59%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.