Kabelarea för 63 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 35 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 5.11V (1.28%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.39V (1.35%)
Voltage at Load394.9 VLine Loss: 557.4 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A54.49 V (13.62%)345.5 V89.88 V (22.47%)5945.6 WDrop High
2.5 mm²24 A18 A32.69 V (8.17%)367.3 V53.93 V (13.48%)3567.3 WDrop High
4 mm²32 A25 A20.43 V (5.11%)379.6 V33.7 V (8.43%)2229.6 WDrop High
6 mm²41 A32 A13.62 V (3.41%)386.4 V22.47 V (5.62%)1486.4 WDrop High
10 mm²57 A44 A8.17 V (2.04%)391.8 V13.48 V (3.37%)891.8 WDrop High
16 mm²76 A59 A5.11 V (1.28%)394.9 V8.43 V (2.11%)557.4 W✓ OK (≤3%)
25 mm²101 A78 A3.27 V (0.82%)396.7 V5.39 V (1.35%)356.7 W✓ OK (≤3%)
35 mm²125 A97 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
50 mm²151 A118 A1.63 V (0.41%)398.4 V2.7 V (0.67%)178.4 W✓ OK (≤3%)
70 mm²192 A150 A1.17 V (0.29%)398.8 V1.93 V (0.48%)127.4 W✓ OK (≤3%)
95 mm²232 A181 A0.86 V (0.22%)399.1 V1.42 V (0.35%)93.9 W✓ OK (≤3%)
120 mm²269 A210 A0.68 V (0.17%)399.3 V1.12 V (0.28%)74.3 W✓ OK (≤3%)
150 mm²309 A241 A0.54 V (0.14%)399.5 V0.9 V (0.22%)59.5 W✓ OK (≤3%)
185 mm²353 A275 A0.44 V (0.11%)399.6 V0.73 V (0.18%)48.2 W✓ OK (≤3%)
240 mm²415 A324 A0.34 V (0.09%)399.7 V0.56 V (0.14%)37.2 W✓ OK (≤3%)
300 mm²477 A372 A0.27 V (0.07%)399.7 V0.45 V (0.11%)29.7 W✓ OK (≤3%)
400 mm²570 A445 A0.2 V (0.05%)399.8 V0.34 V (0.08%)22.3 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 63A vid 35 meter (400V)?

För 63 Ampere över 35 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.11V / 1.28%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.