⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 63 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 45 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.57V (1.64%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.93V (1.73%)
Voltage at Load393.4 VLine Loss: 716.7 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A70.05 V (17.51%)329.9 V115.56 V (28.89%)7644.3 WDrop High
2.5 mm²24 A18 A42.03 V (10.51%)358.0 V69.33 V (17.33%)4586.6 WDrop High
4 mm²32 A25 A26.27 V (6.57%)373.7 V43.33 V (10.83%)2866.6 WDrop High
6 mm²41 A32 A17.51 V (4.38%)382.5 V28.89 V (7.22%)1911.1 WDrop High
10 mm²57 A44 A10.51 V (2.63%)389.5 V17.33 V (4.33%)1146.6 WDrop High
16 mm²76 A59 A6.57 V (1.64%)393.4 V10.83 V (2.71%)716.7 W✓ OK (≤3%)
25 mm²101 A78 A4.2 V (1.05%)395.8 V6.93 V (1.73%)458.7 W✓ OK (≤3%)
35 mm²125 A97 A3.0 V (0.75%)397.0 V4.95 V (1.24%)327.6 W✓ OK (≤3%)
50 mm²151 A118 A2.1 V (0.53%)397.9 V3.47 V (0.87%)229.3 W✓ OK (≤3%)
70 mm²192 A150 A1.5 V (0.38%)398.5 V2.48 V (0.62%)163.8 W✓ OK (≤3%)
95 mm²232 A181 A1.11 V (0.28%)398.9 V1.82 V (0.46%)120.7 W✓ OK (≤3%)
120 mm²269 A210 A0.88 V (0.22%)399.1 V1.44 V (0.36%)95.6 W✓ OK (≤3%)
150 mm²309 A241 A0.7 V (0.18%)399.3 V1.16 V (0.29%)76.4 W✓ OK (≤3%)
185 mm²353 A275 A0.57 V (0.14%)399.4 V0.94 V (0.23%)62.0 W✓ OK (≤3%)
240 mm²415 A324 A0.44 V (0.11%)399.6 V0.72 V (0.18%)47.8 W✓ OK (≤3%)
300 mm²477 A372 A0.35 V (0.09%)399.6 V0.58 V (0.14%)38.2 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (0.07%)399.7 V0.43 V (0.11%)28.7 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 63A vid 45 meter (400V)?

För 63 Ampere över 45 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.57V / 1.64%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.