🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.29%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 5.7V (2.37%)
Voltage at Load End234.5 VLoss: 5.49 V (823.1 W)
Power & Breaker (125%)36.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.12 V (58.8%)98.9 V232.78 V (96.99%)21167.5 WDrop/Amp High
12 AWG3.31 mm²20 A88.68 V (36.95%)151.3 V146.28 V (60.95%)13301.6 WDrop/Amp High
10 AWG5.26 mm²30 A55.8 V (23.25%)184.2 V92.05 V (38.35%)8370.4 WDrop/Amp High
8 AWG8.37 mm²50 A35.07 V (14.61%)204.9 V57.85 V (24.1%)5260.3 WDrop/Amp High
6 AWG13.3 mm²65 A22.07 V (9.2%)217.9 V36.4 V (15.17%)3310.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.88 V (5.78%)226.1 V22.89 V (9.54%)2081.7 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (4.59%)229.0 V18.15 V (7.56%)1650.9 WDrop/Amp High
2 AWG33.62 mm²115 A8.73 V (3.64%)231.3 V14.4 V (6.0%)1309.6 WDrop/Amp High
1 AWG42.41 mm²130 A6.92 V (2.88%)233.1 V11.42 V (4.76%)1038.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (2.29%)234.5 V9.05 V (3.77%)823.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.35 V (1.81%)235.6 V7.18 V (2.99%)652.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.45 V (1.44%)236.5 V5.7 V (2.37%)517.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.74 V (1.14%)237.3 V4.52 V (1.88%)410.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.32 V (0.97%)237.7 V3.82 V (1.59%)347.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.93 V (0.8%)238.1 V3.19 V (1.33%)289.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.66 V (0.69%)238.3 V2.73 V (1.14%)248.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.45 V (0.6%)238.6 V2.39 V (1.0%)217.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.16 V (0.48%)238.8 V1.91 V (0.8%)173.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.97 V (0.4%)239.0 V1.59 V (0.66%)144.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.77 V (0.32%)239.2 V1.27 V (0.53%)115.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.58 V (0.24%)239.4 V0.96 V (0.4%)86.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 150 feet one-way at 240V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.49V (2.29%) and delivers 234.5V at the load.

What size aluminum wire is required for 150 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 5.7V (2.37%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.