⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 1.38%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.82V (1.59%)
Voltage at Load End236.7 VLoss: 3.31 V (993.3 W)
Power & Breaker (125%)72.0 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A282.23 V (117.6%)0.0 V465.55 V (193.98%)84669.9 WDrop/Amp High
12 AWG3.31 mm²20 A177.35 V (73.9%)62.6 V292.55 V (121.9%)53206.5 WDrop/Amp High
10 AWG5.26 mm²30 A111.61 V (46.5%)128.4 V184.1 V (76.71%)33481.6 WDrop/Amp High
8 AWG8.37 mm²50 A70.14 V (29.22%)169.9 V115.69 V (48.21%)21041.0 WDrop/Amp High
6 AWG13.3 mm²65 A44.14 V (18.39%)195.9 V72.81 V (30.34%)13241.6 WDrop/Amp High
4 AWG21.15 mm²85 A27.76 V (11.57%)212.2 V45.78 V (19.08%)8326.9 WDrop/Amp High
3 AWG26.67 mm²100 A22.01 V (9.17%)218.0 V36.31 V (15.13%)6603.4 WDrop/Amp High
2 AWG33.62 mm²115 A17.46 V (7.28%)222.5 V28.8 V (12.0%)5238.4 WDrop/Amp High
1 AWG42.41 mm²130 A13.84 V (5.77%)226.2 V22.83 V (9.51%)4152.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.97 V (4.57%)229.0 V18.1 V (7.54%)3292.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.71 V (3.63%)231.3 V14.36 V (5.98%)2611.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.91 V (2.88%)233.1 V11.39 V (4.75%)2071.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.48 V (2.28%)234.5 V9.03 V (3.76%)1642.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.63 V (1.93%)235.4 V7.64 V (3.18%)1390.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.86 V (1.61%)236.1 V6.37 V (2.65%)1158.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.31 V (1.38%)236.7 V5.46 V (2.28%)993.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.9 V (1.21%)237.1 V4.78 V (1.99%)868.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.32 V (0.97%)237.7 V3.82 V (1.59%)695.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.93 V (0.8%)238.1 V3.19 V (1.33%)579.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.54 V (0.64%)238.5 V2.55 V (1.06%)463.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.16 V (0.48%)238.8 V1.91 V (0.8%)347.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 150 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 3.31V (1.38%) and delivers 236.7V at the load.

What size aluminum wire is required for 300 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.82V (1.59%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.