⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 60 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 1.47%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.66V (1.53%)
Voltage at Load End236.5 VLoss: 3.53 V (211.9 W)
Power & Breaker (125%)14.4 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.58 V (9.41%)217.4 V37.24 V (15.52%)1354.7 WDrop/Amp High
12 AWG3.31 mm²20 A14.19 V (5.91%)225.8 V23.4 V (9.75%)851.3 WDrop/Amp High
10 AWG5.26 mm²30 A8.93 V (3.72%)231.1 V14.73 V (6.14%)535.7 WDrop/Amp High
8 AWG8.37 mm²50 A5.61 V (2.34%)234.4 V9.26 V (3.86%)336.7 WDrop/Amp High
6 AWG13.3 mm²65 A3.53 V (1.47%)236.5 V5.82 V (2.43%)211.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.22 V (0.93%)237.8 V3.66 V (1.53%)133.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.76 V (0.73%)238.2 V2.9 V (1.21%)105.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.4 V (0.58%)238.6 V2.3 V (0.96%)83.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.11 V (0.46%)238.9 V1.83 V (0.76%)66.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.88 V (0.37%)239.1 V1.45 V (0.6%)52.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.7 V (0.29%)239.3 V1.15 V (0.48%)41.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.55 V (0.23%)239.4 V0.91 V (0.38%)33.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.44 V (0.18%)239.6 V0.72 V (0.3%)26.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.15%)239.6 V0.61 V (0.25%)22.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.13%)239.7 V0.51 V (0.21%)18.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.11%)239.7 V0.44 V (0.18%)15.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.1%)239.8 V0.38 V (0.16%)13.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.08%)239.8 V0.31 V (0.13%)11.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.06%)239.8 V0.25 V (0.11%)9.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.05%)239.9 V0.2 V (0.08%)7.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.04%)239.9 V0.15 V (0.06%)5.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 60 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.53V (1.47%) and delivers 236.5V at the load.

What size aluminum wire is required for 60 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.66V (1.53%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.