⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)3 AWGDrop: 5.81V (2.42%)
Voltage at Load End232.9 VLoss: 7.06 V (423.7 W)
Power & Breaker (125%)14.4 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A45.16 V (18.82%)194.8 V74.49 V (31.04%)2709.4 WDrop/Amp High
12 AWG3.31 mm²20 A28.38 V (11.82%)211.6 V46.81 V (19.5%)1702.6 WDrop/Amp High
10 AWG5.26 mm²30 A17.86 V (7.44%)222.1 V29.46 V (12.27%)1071.4 WDrop/Amp High
8 AWG8.37 mm²50 A11.22 V (4.68%)228.8 V18.51 V (7.71%)673.3 WDrop/Amp High
6 AWG13.3 mm²65 A7.06 V (2.94%)232.9 V11.65 V (4.85%)423.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.44 V (1.85%)235.6 V7.33 V (3.05%)266.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.52 V (1.47%)236.5 V5.81 V (2.42%)211.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.79 V (1.16%)237.2 V4.61 V (1.92%)167.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.21 V (0.92%)237.8 V3.65 V (1.52%)132.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.76 V (0.73%)238.2 V2.9 V (1.21%)105.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.39 V (0.58%)238.6 V2.3 V (0.96%)83.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.1 V (0.46%)238.9 V1.82 V (0.76%)66.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.88 V (0.37%)239.1 V1.45 V (0.6%)52.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.74 V (0.31%)239.3 V1.22 V (0.51%)44.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.62 V (0.26%)239.4 V1.02 V (0.42%)37.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.53 V (0.22%)239.5 V0.87 V (0.36%)31.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.46 V (0.19%)239.5 V0.76 V (0.32%)27.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.37 V (0.15%)239.6 V0.61 V (0.25%)22.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.31 V (0.13%)239.7 V0.51 V (0.21%)18.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.25 V (0.1%)239.8 V0.41 V (0.17%)14.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.19 V (0.08%)239.8 V0.31 V (0.13%)11.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 120 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 7.06V (2.94%) and delivers 232.9V at the load.

What size aluminum wire is required for 60 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 5.81V (2.42%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.