⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.34%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.82V (2.43%)
Voltage at Load End234.4 VLoss: 5.61 V (168.3 W)
Power & Breaker (125%)7.2 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.58 V (9.41%)217.4 V37.24 V (15.52%)677.4 WDrop/Amp High
12 AWG3.31 mm²20 A14.19 V (5.91%)225.8 V23.4 V (9.75%)425.7 WDrop/Amp High
10 AWG5.26 mm²30 A8.93 V (3.72%)231.1 V14.73 V (6.14%)267.9 W~ ≤5%
8 AWG8.37 mm²50 A5.61 V (2.34%)234.4 V9.26 V (3.86%)168.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.53 V (1.47%)236.5 V5.82 V (2.43%)105.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.22 V (0.93%)237.8 V3.66 V (1.53%)66.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.76 V (0.73%)238.2 V2.9 V (1.21%)52.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.4 V (0.58%)238.6 V2.3 V (0.96%)41.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.11 V (0.46%)238.9 V1.83 V (0.76%)33.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.88 V (0.37%)239.1 V1.45 V (0.6%)26.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.7 V (0.29%)239.3 V1.15 V (0.48%)20.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.55 V (0.23%)239.4 V0.91 V (0.38%)16.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.44 V (0.18%)239.6 V0.72 V (0.3%)13.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.15%)239.6 V0.61 V (0.25%)11.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.13%)239.7 V0.51 V (0.21%)9.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.11%)239.7 V0.44 V (0.18%)7.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.1%)239.8 V0.38 V (0.16%)7.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.08%)239.8 V0.31 V (0.13%)5.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.06%)239.8 V0.25 V (0.11%)4.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.05%)239.9 V0.2 V (0.08%)3.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.04%)239.9 V0.15 V (0.06%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 120 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.61V (2.34%) and delivers 234.4V at the load.

What size aluminum wire is required for 30 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.82V (2.43%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.