🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.06%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 2.63V (1.1%)
Voltage at Load End237.5 VLoss: 2.54 V (444.4 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A82.32 V (34.3%)157.7 V135.79 V (56.58%)14405.6 WDrop/Amp High
12 AWG3.31 mm²20 A51.73 V (21.55%)188.3 V85.33 V (35.55%)9052.5 WDrop/Amp High
10 AWG5.26 mm²30 A32.55 V (13.56%)207.4 V53.69 V (22.37%)5696.5 WDrop/Amp High
8 AWG8.37 mm²50 A20.46 V (8.52%)219.5 V33.74 V (14.06%)3579.9 WDrop/Amp High
6 AWG13.3 mm²65 A12.87 V (5.36%)227.1 V21.24 V (8.85%)2252.9 WDrop/Amp High
4 AWG21.15 mm²85 A8.1 V (3.37%)231.9 V13.35 V (5.56%)1416.7 WDrop/Amp High
3 AWG26.67 mm²100 A6.42 V (2.67%)233.6 V10.59 V (4.41%)1123.5 WDrop/Amp High
2 AWG33.62 mm²115 A5.09 V (2.12%)234.9 V8.4 V (3.5%)891.2 WDrop/Amp High
1 AWG42.41 mm²130 A4.04 V (1.68%)236.0 V6.66 V (2.77%)706.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.2 V (1.33%)236.8 V5.28 V (2.2%)560.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.54 V (1.06%)237.5 V4.19 V (1.75%)444.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.01 V (0.84%)238.0 V3.32 V (1.38%)352.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.6 V (0.67%)238.4 V2.63 V (1.1%)279.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.35 V (0.56%)238.6 V2.23 V (0.93%)236.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.13 V (0.47%)238.9 V1.86 V (0.77%)197.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.97 V (0.4%)239.0 V1.59 V (0.66%)169.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.84 V (0.35%)239.2 V1.39 V (0.58%)147.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.68 V (0.28%)239.3 V1.11 V (0.46%)118.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.56 V (0.23%)239.4 V0.93 V (0.39%)98.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.45 V (0.19%)239.5 V0.74 V (0.31%)78.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.34 V (0.14%)239.7 V0.56 V (0.23%)59.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 75 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 2.54V (1.06%) and delivers 237.5V at the load.

What size aluminum wire is required for 175 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 2.63V (1.1%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.