⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)10 AWGDrop: 6.14V (2.56%)
Voltage at Load End234.1 VLoss: 5.91 V (118.2 W)
Power & Breaker (125%)4.8 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.41 V (3.92%)230.6 V15.52 V (6.47%)188.2 WDrop/Amp High
12 AWG3.31 mm²20 A5.91 V (2.46%)234.1 V9.75 V (4.06%)118.2 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A3.72 V (1.55%)236.3 V6.14 V (2.56%)74.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.34 V (0.97%)237.7 V3.86 V (1.61%)46.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.47 V (0.61%)238.5 V2.43 V (1.01%)29.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.93 V (0.39%)239.1 V1.53 V (0.64%)18.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.73 V (0.31%)239.3 V1.21 V (0.5%)14.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.58 V (0.24%)239.4 V0.96 V (0.4%)11.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.46 V (0.19%)239.5 V0.76 V (0.32%)9.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.37 V (0.15%)239.6 V0.6 V (0.25%)7.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.29 V (0.12%)239.7 V0.48 V (0.2%)5.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.23 V (0.1%)239.8 V0.38 V (0.16%)4.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.18 V (0.08%)239.8 V0.3 V (0.13%)3.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.15 V (0.06%)239.8 V0.25 V (0.11%)3.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.05%)239.9 V0.21 V (0.09%)2.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.05%)239.9 V0.18 V (0.08%)2.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.04%)239.9 V0.16 V (0.07%)1.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.03%)239.9 V0.13 V (0.05%)1.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.03%)239.9 V0.11 V (0.04%)1.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.02%)239.9 V0.08 V (0.04%)1.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)240.0 V0.06 V (0.03%)0.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 75 feet one-way at 240V (1-Phase), you need 12 AWG copper wire. This produces a voltage drop of 5.91V (2.46%) and delivers 234.1V at the load.

What size aluminum wire is required for 20 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 6.14V (2.56%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.