🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.78%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 4.43V (1.84%)
Voltage at Load End235.7 VLoss: 4.27 V (469.5 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A68.99 V (28.75%)171.0 V113.8 V (47.42%)7588.9 WDrop/Amp High
12 AWG3.31 mm²20 A43.35 V (18.06%)196.6 V71.51 V (29.8%)4768.9 WDrop/Amp High
10 AWG5.26 mm²30 A27.28 V (11.37%)212.7 V45.0 V (18.75%)3000.9 WDrop/Amp High
8 AWG8.37 mm²50 A17.14 V (7.14%)222.9 V28.28 V (11.78%)1885.9 WDrop/Amp High
6 AWG13.3 mm²65 A10.79 V (4.5%)229.2 V17.8 V (7.42%)1186.8 WDrop/Amp High
4 AWG21.15 mm²85 A6.78 V (2.83%)233.2 V11.19 V (4.66%)746.3 WDrop/Amp High
3 AWG26.67 mm²100 A5.38 V (2.24%)234.6 V8.88 V (3.7%)591.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.27 V (1.78%)235.7 V7.04 V (2.93%)469.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.38 V (1.41%)236.6 V5.58 V (2.33%)372.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.68 V (1.12%)237.3 V4.43 V (1.84%)295.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.13 V (0.89%)237.9 V3.51 V (1.46%)234.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.69 V (0.7%)238.3 V2.78 V (1.16%)185.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.34 V (0.56%)238.7 V2.21 V (0.92%)147.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.13 V (0.47%)238.9 V1.87 V (0.78%)124.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.94 V (0.39%)239.1 V1.56 V (0.65%)103.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.81 V (0.34%)239.2 V1.34 V (0.56%)89.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.71 V (0.29%)239.3 V1.17 V (0.49%)77.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.57 V (0.24%)239.4 V0.93 V (0.39%)62.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.47 V (0.2%)239.5 V0.78 V (0.32%)51.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.38 V (0.16%)239.6 V0.62 V (0.26%)41.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.12%)239.7 V0.47 V (0.19%)31.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 100 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 4.27V (1.78%) and delivers 235.7V at the load.

What size aluminum wire is required for 110 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 4.43V (1.84%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.