⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.53%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 1.33V (0.55%)
Voltage at Load End238.7 VLoss: 1.28 V (140.9 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.7 V (8.62%)219.3 V34.14 V (14.23%)2276.7 WDrop/Amp High
12 AWG3.31 mm²20 A13.01 V (5.42%)227.0 V21.45 V (8.94%)1430.7 WDrop/Amp High
10 AWG5.26 mm²30 A8.18 V (3.41%)231.8 V13.5 V (5.63%)900.3 WDrop/Amp High
8 AWG8.37 mm²50 A5.14 V (2.14%)234.9 V8.48 V (3.54%)565.8 WDrop/Amp High
6 AWG13.3 mm²65 A3.24 V (1.35%)236.8 V5.34 V (2.22%)356.1 WDrop/Amp High
4 AWG21.15 mm²85 A2.04 V (0.85%)238.0 V3.36 V (1.4%)223.9 WDrop/Amp High
3 AWG26.67 mm²100 A1.61 V (0.67%)238.4 V2.66 V (1.11%)177.6 WDrop/Amp High
2 AWG33.62 mm²115 A1.28 V (0.53%)238.7 V2.11 V (0.88%)140.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.02 V (0.42%)239.0 V1.67 V (0.7%)111.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.8 V (0.34%)239.2 V1.33 V (0.55%)88.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.64 V (0.27%)239.4 V1.05 V (0.44%)70.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.51 V (0.21%)239.5 V0.84 V (0.35%)55.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.4 V (0.17%)239.6 V0.66 V (0.28%)44.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.34 V (0.14%)239.7 V0.56 V (0.23%)37.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.28 V (0.12%)239.7 V0.47 V (0.19%)31.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (0.1%)239.8 V0.4 V (0.17%)26.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (0.09%)239.8 V0.35 V (0.15%)23.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.17 V (0.07%)239.8 V0.28 V (0.12%)18.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.06%)239.9 V0.23 V (0.1%)15.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.05%)239.9 V0.19 V (0.08%)12.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.04%)239.9 V0.14 V (0.06%)9.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 30 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 1.28V (0.53%) and delivers 238.7V at the load.

What size aluminum wire is required for 110 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 1.33V (0.55%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.