🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.48%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 1.2V (0.5%)
Voltage at Load End238.8 VLoss: 1.15 V (144.2 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.52 V (9.8%)216.5 V38.8 V (16.17%)2939.9 WDrop/Amp High
12 AWG3.31 mm²20 A14.78 V (6.16%)225.2 V24.38 V (10.16%)1847.4 WDrop/Amp High
10 AWG5.26 mm²30 A9.3 V (3.88%)230.7 V15.34 V (6.39%)1162.6 WDrop/Amp High
8 AWG8.37 mm²50 A5.84 V (2.44%)234.2 V9.64 V (4.02%)730.6 WDrop/Amp High
6 AWG13.3 mm²65 A3.68 V (1.53%)236.3 V6.07 V (2.53%)459.8 WDrop/Amp High
4 AWG21.15 mm²85 A2.31 V (0.96%)237.7 V3.82 V (1.59%)289.1 WDrop/Amp High
3 AWG26.67 mm²100 A1.83 V (0.76%)238.2 V3.03 V (1.26%)229.3 WDrop/Amp High
2 AWG33.62 mm²115 A1.46 V (0.61%)238.5 V2.4 V (1.0%)181.9 WDrop/Amp High
1 AWG42.41 mm²130 A1.15 V (0.48%)238.8 V1.9 V (0.79%)144.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.91 V (0.38%)239.1 V1.51 V (0.63%)114.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.73 V (0.3%)239.3 V1.2 V (0.5%)90.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.58 V (0.24%)239.4 V0.95 V (0.4%)71.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.46 V (0.19%)239.5 V0.75 V (0.31%)57.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.39 V (0.16%)239.6 V0.64 V (0.27%)48.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.32 V (0.13%)239.7 V0.53 V (0.22%)40.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (0.11%)239.7 V0.46 V (0.19%)34.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.24 V (0.1%)239.8 V0.4 V (0.17%)30.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.08%)239.8 V0.32 V (0.13%)24.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.07%)239.8 V0.27 V (0.11%)20.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.05%)239.9 V0.21 V (0.09%)16.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.04%)239.9 V0.16 V (0.07%)12.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 30 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 1.15V (0.48%) and delivers 238.8V at the load.

What size aluminum wire is required for 125 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 1.2V (0.5%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.