🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.64%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 1.6V (0.66%)
Voltage at Load End238.5 VLoss: 1.54 V (192.3 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A31.36 V (13.07%)208.6 V51.73 V (21.55%)3919.9 WDrop/Amp High
12 AWG3.31 mm²20 A19.71 V (8.21%)220.3 V32.51 V (13.54%)2463.3 WDrop/Amp High
10 AWG5.26 mm²30 A12.4 V (5.17%)227.6 V20.46 V (8.52%)1550.1 WDrop/Amp High
8 AWG8.37 mm²50 A7.79 V (3.25%)232.2 V12.85 V (5.36%)974.1 WDrop/Amp High
6 AWG13.3 mm²65 A4.9 V (2.04%)235.1 V8.09 V (3.37%)613.0 WDrop/Amp High
4 AWG21.15 mm²85 A3.08 V (1.29%)236.9 V5.09 V (2.12%)385.5 WDrop/Amp High
3 AWG26.67 mm²100 A2.45 V (1.02%)237.6 V4.03 V (1.68%)305.7 WDrop/Amp High
2 AWG33.62 mm²115 A1.94 V (0.81%)238.1 V3.2 V (1.33%)242.5 WDrop/Amp High
1 AWG42.41 mm²130 A1.54 V (0.64%)238.5 V2.54 V (1.06%)192.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.22 V (0.51%)238.8 V2.01 V (0.84%)152.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.97 V (0.4%)239.0 V1.6 V (0.66%)120.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.77 V (0.32%)239.2 V1.27 V (0.53%)95.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.61 V (0.25%)239.4 V1.0 V (0.42%)76.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.51 V (0.21%)239.5 V0.85 V (0.35%)64.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.43 V (0.18%)239.6 V0.71 V (0.29%)53.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.37 V (0.15%)239.6 V0.61 V (0.25%)46.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.32 V (0.13%)239.7 V0.53 V (0.22%)40.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.26 V (0.11%)239.7 V0.42 V (0.18%)32.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.21 V (0.09%)239.8 V0.35 V (0.15%)26.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.17 V (0.07%)239.8 V0.28 V (0.12%)21.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.13 V (0.05%)239.9 V0.21 V (0.09%)16.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 40 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 1.54V (0.64%) and delivers 238.5V at the load.

What size aluminum wire is required for 125 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 1.6V (0.66%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.