🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.14V (2.56%)
Voltage at Load End234.1 VLoss: 5.92 V (651.3 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A120.73 V (50.31%)119.3 V199.15 V (82.98%)13280.6 WDrop/Amp High
12 AWG3.31 mm²20 A75.87 V (31.61%)164.1 V125.15 V (52.14%)8345.5 WDrop/Amp High
10 AWG5.26 mm²30 A47.74 V (19.89%)192.3 V78.75 V (32.81%)5251.7 WDrop/Amp High
8 AWG8.37 mm²50 A30.0 V (12.5%)210.0 V49.49 V (20.62%)3300.3 WDrop/Amp High
6 AWG13.3 mm²65 A18.88 V (7.87%)221.1 V31.15 V (12.98%)2077.0 WDrop/Amp High
4 AWG21.15 mm²85 A11.87 V (4.95%)228.1 V19.59 V (8.16%)1306.1 WDrop/Amp High
3 AWG26.67 mm²100 A9.42 V (3.92%)230.6 V15.53 V (6.47%)1035.8 WDrop/Amp High
2 AWG33.62 mm²115 A7.47 V (3.11%)232.5 V12.32 V (5.13%)821.6 W~ ≤5%
1 AWG42.41 mm²130 A5.92 V (2.47%)234.1 V9.77 V (4.07%)651.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.69 V (1.96%)235.3 V7.74 V (3.23%)516.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.72 V (1.55%)236.3 V6.14 V (2.56%)409.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.95 V (1.23%)237.0 V4.87 V (2.03%)324.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.34 V (0.98%)237.7 V3.86 V (1.61%)257.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.98 V (0.83%)238.0 V3.27 V (1.36%)218.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.65 V (0.69%)238.3 V2.73 V (1.14%)181.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.42 V (0.59%)238.6 V2.34 V (0.97%)155.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.24 V (0.52%)238.8 V2.04 V (0.85%)136.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.99 V (0.41%)239.0 V1.63 V (0.68%)109.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.83 V (0.34%)239.2 V1.36 V (0.57%)90.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.66 V (0.28%)239.3 V1.09 V (0.45%)72.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.21%)239.5 V0.82 V (0.34%)54.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 175 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.92V (2.47%) and delivers 234.1V at the load.

What size aluminum wire is required for 110 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.14V (2.56%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.